H07V-U
PVC insulated conductor – single wire (solid)
|
JUS mark:
P
|
|
|
Application |
Standards |
|
Insulated conductor is used for laying in electric-installation tubes, under and on plaster installation in dry rooms and in closed installation conduits. Direct laying in cable guides is not permitted. Also applied for internal wiring of distribution and switching boxes equipment, same as for protective laying for lighting of nominal voltage up to 1000 V alternating current, or up to 750 V direct current against earth.
|
HRN HD 21.3 S3
IEC 60227-3
DIN VDE 0281 part 3
|
|
Construction |
|
Technical data |
Temperature range: |
|
during installation:
|
+5 °C up to+70 °C |
fixed installed: |
-30 °C up to+70 °C |
at short circuit of max. 5 s.: |
up tp 160 °C |
ambient temperature at storage: |
up pt 40 °C |
Nominal voltage: |
Uο/U = 450/750 V |
Test voltage: |
2500 V |
Minimal inner bending radius: |
4D |
Behaviour in fire: |
IEC 60332-1 |
Dimensions – conductor cross-section |
Construction of individual conductor |
External diameter |
Insulation thickness |
Conductor resistance at 20 °C |
Specific. el. resistance of insulation at 70°C |
Cu weight |
Cable weight |
Packing*
|
|
nominal
|
min-max.
|
nominal
|
max.
|
min.
|
|
approx
|
|
mm²
|
n x mm
|
mm
|
mm
|
Ω/km
|
MΩkm
|
kg/km
|
kg/km
|
|
1,5 |
1 x 1,38 |
2,6 - 3,2 |
0,7 |
12,10 |
0,011 |
14,4 |
20 |
c.100 |
2,5 |
1 x 1,78 |
3,2 - 3,9 |
0,8 |
7,41 |
0,010 |
24,0 |
31 |
c.100 |
4 |
1 x 2,26 |
3,6 - 4,4 |
0,8 |
4,61 |
0,0087 |
38,4 |
46 |
c.100 |
6 |
1 x 2,70 |
4,1 - 5,0 |
0,8 |
3,08 |
0,0070 |
57,6 |
65 |
c.100 |
10 |
1 x 3,5 |
5,3 - 6,4 |
1,0 |
1,83 |
0,0072 |
96,0 |
110 |
c.100 |
*)
*) Packing: c.100 = coil 100 m