NYCYPower and signalling cable 0,6/1 kV, PVC insulated and sheathed, with concentric protective Cu conductor |
JUS mark:PP40 |
Application |
Standards |
|
Distribution and signalling power cable for static outdoor application (with protection against direct UV-irradiation), in ground, in water, within facilities, in cable canals, in concrete, in conditions requiring increased electric protection and protection against mechanical damages. Used in electric power plants, transformer stations, industrial plants, metropolitan networks and other electric plants and for connection of signalling devices in industry, traffic and similar. Concentric conductor can be used as neutral, protective or earth connection, and if there is a danger of damages caused by digging, it acts as protection against contact voltage in case of rough insulation damage. |
HRN HD 603 S1
cables with 6 and more conductors: |
NYCY 117.09 Kb |
Construction |
Technical data |
Conductor: | Cu, class 1 acc. to HRN HD 383 / IEC 60228 / DIN VDE 0295, solid, round (RE) | |
Insulation: | PVC compound DIV-4 acc. to HRN HD 603.1, concentrically stranded cores, colour marked acc. to HRN HD 308 S2 / VDE 0293-308, without protective yellow-green conductor | |
Filler: | spouted elastomer or plastomer compound or wrapped thermoplastic tapes | |
Concentric conductor: | in inner layer round copper wires, in external layer copper tape wrapped in counter-helix | |
Sheath: | PVC compound DMV-5 acc. to HRN HD 603.1 | |
sheath colour: | black | |
Core colour marking: | HRN HD 308 S2 / VDE 0293-308 | |
Temperature range: | |
during installation: |
-5 °C up to +50 °C |
fixed installed: | -30 °C up to +70 °C |
at short circuit of max. 5 s: | up to 160 °C |
Nominal voltage: | Uο/U = 0,6/1 kV |
Test voltage: | 4 kV |
Max. operating voltage in three-phase systems: | 1,2 kV |
Maximal tensile strength: | 50 N/mm² |
Behaviour in fire: | IEC 60332-1 |
Minimal inner bending radius: | |
single core: | 15D |
multi core: | 12D |
Dimensions – number of cores x conductor cross-section | Construction | Conductor diameter | External diameter | Insulation thickness | Sheath thickness | Short circuit current 1s | Cu weight | Cable weight | Packing* |
nominal | min-max. | nominal | nominal | nominal | approx. | ||||
N x mm² | mm | mm | mm | mm | kA | kg/km | Kg/km | ||
Power NYCY | |||||||||
2 x 1,5/1,5 | RE | 1,5 | 12,0 - 13,0 | 0,8 | 1,8 | 0,173 | 52 | 200 | CUT |
2 x 2,5/2,5 | RE | 1,9 | 13,3 - 14 | 0,8 | 1,8 | 0,288 | 80 | 260 | CUT |
2 x 4/4 | RE | 2,4 | 15,3 - 16,0 | 1 | 1,8 | 0,46 | 123 | 350 | CUT |
2 x 6/6 | RE | 2,9 | 16,1 - 17,5 | 1 | 1,8 | 0,69 | 182 | 430 | CUT |
2 x 10/10 | RE | 3,7 | 18,5 - 19,5 | 1 | 1,8 | 1,15 | 312 | 520 | CUT |
2 x 16/16 | RE | 4,6 | 20,5 | 1 | 1,8 | 1,84 | 489 | 720 | CUT |
3 x 1,5/1,5 | RE | 1,5 | 13 - 17 | 0,8 | 1,8 | 0,173 | 66 | 220 | CUT |
3 x 2,5/2,5 | RE | 1,9 | 14 - 17 | 0,8 | 1,8 | 0,288 | 104 | 280 | CUT |
3 x 4/4 | RE | 2,4 | 15 - 18 | 1 | 1,8 | 0,46 | 161 | 390 | CUT |
3 x 6/6 | RE | 2,9 | 16 - 20 | 1 | 1,8 | 0,69 | 240 | 500 | CUT |
3 x 10/10 | RE | 3,7 | 18 - 22 | 1 | 1,8 | 1,15 | 408 | 680 | CUT |
3 x 16/16 | RE | 4,6 | 16 - 24 | 1 | 1,8 | 1,84 | 643 | 1010 | CUT |
4 x 1,5/1,5 | RE | 1,5 | 14 - 18 | 0,8 | 1,8 | 0,173 | 81 | 250 | CUT |
4 x 2,5/2,5 | RE | 1,9 | 15 - 19 | 0,8 | 1,8 | 0,288 | 128 | 340 | CUT |
4 x 4/4 | RE | 2,4 | 16 - 20 | 1 | 1,8 | 0,46 | 200 | 460 | CUT |
4 x 6/6 | RE | 2,9 | 17 - 21 | 1 | 1,8 | 0,69 | 297 | 580 | CUT |
4 x 10/10 | RE | 3,7 | 19 - 23 | 1 | 1,8 | 1,15 | 504 | 765 | CUT |
4 x 16/16 | RE | 4,6 | 21 - 25 | 1 | 1,8 | 1,84 | 796 | 1060 | CUT |
5 x 1,5/1,5 | RE | 1,5 | 15 - 16 | 0,8 | 1,8 | 0,173 | 95 | 330 | CUT |
5 x 2,5/2,5 | RE | 1,9 | 16 - 17 | 0,8 | 1,8 | 0,288 | 152 | 400 | CUT |
5 x 4/4 | RE | 2,4 | 19 | 1 | 1,8 | 0,46 | 238 | 550 | CUT |
5 x 6/6 | RE | 2,9 | 20 - 22 | 1 | 1,8 | 0,69 | 355 | 700 | CUT |
5 x 10/10 | RE | 3,7 | 22,5 | 1 | 1,8 | 1,15 | 600 | 1000 | CUT |
Signalnini NYCY | |||||||||
7 x 1,5/2,5 | RE | 1,5 | 14 - 19 | 0,8 | 1,8 | 0,173 | 133 | 350 | CUT |
8 x 1,5/2,5 | RE | 1,5 | 17 | 0,8 | 1,8 | 0,173 | 147 | 400 | CUT |
10 x 1,5/2,5 | RE | 1,5 | 18 - 23 | 0,8 | 1,8 | 0,173 | 176 | 410 | CUT |
12 x 1,5/2,5 | RE | 1,5 | 19 - 24 | 0,8 | 1,8 | 0,173 | 205 | 470 | CUT |
14 x 1,5/2,5 | RE | 1,5 | 20 - 25 | 0,8 | 1,8 | 0,173 | 234 | 520 | CUT |
16 x 1,5/2,5 | RE | 1,5 | 20 | 0,8 | 1,8 | 0,173 | 276 | 620 | CUT |
19 x 1,5/4 | RE | 1,5 | 22 - 28 | 0,8 | 1,8 | 0,173 | 320 | 660 | CUT |
21 x 1,5/6 | RE | 1,5 | 22 | 0,8 | 1,8 | 0,173 | 369 | 790 | CUT |
24 x 1,5/6 | RE | 1,5 | 25 - 31 | 0,8 | 1,8 | 0,173 | 413 | 850 | CUT |
30 x 1,5/6 | RE | 1,5 | 32 | 0,8 | 1,8 | 0,173 | 499 | 1020 | CUT |
40 x 1,5/10 | RE | 1,5 | 29 | 0,8 | 1,9 | 0,173 | 696 | 1280 | CUT |
52 x 1,5/10 | RE | 1,5 | 30 | 0,8 | 2,0 | 0,173 | 869 | 1600 | CUT |
61 x 1,5/10 | RE | 1,5 | 32 | 0,8 | 2,1 | 0,173 | 998 | 2000 | CUT |
7 x 2,5/2,5 | RE | 1,9 | 17 - 21 | 0,8 | 1,8 | 0,288 | 200 | 450 | CUT |
8 x 2,5/2,5 | RE | 1,9 | 18 | 0,8 | 1,8 | 0,288 | 224 | 510 | CUT |
10 x 2,5/4 | RE | 1,9 | 20 - 25 | 0,8 | 1,8 | 0,288 | 286 | 600 | CUT |
12 x 2,5/4 | RE | 1,9 | 20 - 25 | 0,8 | 1,8 | 0,288 | 334 | 660 | CUT |
14 x 2,5/6 | RE | 1,9 | 21 - 26 | 0,8 | 1,8 | 0,288 | 403 | 750 | CUT |
16 x 2,5/6 | RE | 1,9 | 22,5 | 0,8 | 1,8 | 0,288 | 451 | 800 | CUT |
19 x 2,5/6 | RE | 1,9 | 23 - 29 | 0,8 | 1,8 | 0,288 | 523 | 940 | CUT |
21 x 2,5/6 | RE | 1,9 | 26 | 0,8 | 1,8 | 0,288 | 571 | 1100 | CUT |
24 x 2,5/10 | RE | 1,9 | 27 - 33 | 0,8 | 1,9 | 0,288 | 696 | 1150 | CUT |
30 x 2,5/10 | RE | 1,9 | 30 | 0,8 | 1,9 | 0,288 | 840 | 1600 | CUT |
40 x 2,5/10 | RE | 1,9 | 35 | 0,8 | 2,0 | 0,288 | 1080 | 1660 | CUT |
52 x 2,5/10 | RE | 1,9 | 38 | 0,8 | 2,2 | 0,288 | 1368 | 2000 | CUT |
61 x 2,5/10 | RE | 1,9 | 40 | 0,8 | 2,3 | 0,288 | 1584 | 2280 | CUT |
7 x 4/4 | RE | 2,4 | 23 | 1,0 | 1,8 | 0,460 | 315 | 600 | CUT |
10 x 4/6 | RE | 2,4 | 27 | 1,0 | 1,8 | 0,460 | 451 | 900 | CUT |
12 x 4/6 | RE | 2,4 | 27 | 1,0 | 1,8 | 0,460 | 528 | 1060 | CUT |
7 x 6/6 | RE | 2,9 | 25 | 1,0 | 1,8 | 0,460 | 470 | 790 | CUT |
*) Packing: CUT = cable in different lengths on drum or reel, possible cutting at required length