H05Z-K, H07Z-K
Halogen-free fine wired conductor, with improved properties under fire
|
|
|
|
Application |
Standards |
|
Halogen-free conductors used for installations in dry environment for wiring of lighting fixtures, tools and other devices in facilities where human lives or valuable property need to be protected against damages caused by fire. Laid on or under plaster, same as in closed installation canals. For inner wiring of switchboards and control panels up to the nominal voltage of 750/1000 V.
advantages:
- halogen-free, no release of toxic or corrosive gases under fire
- reduced smoke occurrence under fire
|
HRN HD 22.9
DIN VDE 0282 part 9
|
|
Construction |
|
Technical data |
Conductor: |
bare or tinned copper conductor, fine wired stranded, class 5 acc. to HRN HD 383 / IEC 60228 / DIN VDE 0295 |
at some producers: |
separator between conductor and insulation |
Insulation: |
cross-linked thermoplastic halogen-free flame retardant polyolefin bond |
|
Conductor color identification: |
acc. to IEC 60446 i.e. EN 60446 (corresponding to DIN VDE 0293) |
possible insulation colors: |
|
Temperature range: |
|
during installation:
|
-5 °C up to +70 °C |
fixed installed: |
-20 °C up to +90 °C |
max. operating temperature: |
90 °C |
at short circuit of max. 5 s: |
up to 250 °C |
Nominal voltage: |
|
H05Z-K: |
Uο/U = 300/500 V |
H07Z-K: |
Uο/U = 450/750 V |
Test voltage: |
2500 V |
Minimal inner bending radius: |
6D |
Flame retardant: |
IEC 60332-1 |
Halogen-free: |
IEC 60754-1 |
Non-corrosive combustion gases: |
IEC 60754-2 |
Low smoke density: |
IEC 61034-2 |
Dimensions – number of cores x conductor cross-section |
Construction of individual conductor |
External diameter |
External diameter |
Conductor diameter |
Insulation thickness |
Conductor resistance at 20 °C |
Cu weight |
Conductor weight |
Packing* |
|
nominal |
min. |
max. |
nominal |
max. |
max. |
|
approx. |
|
N x mm²
|
n x mm |
mm |
mm |
mm |
mm |
Ω/km |
kg/km |
kg/km |
|
H05Z-K |
0,5 |
16 x 0,20 |
2,1 |
2,6 |
0,6 |
1,1 |
39,0000 |
4,8 |
9 |
c.100 |
0,75 |
24 x 0,20 |
2,2 |
2,8 |
0,6 |
1,3 |
26,0000 |
7,2 |
13 |
c.100 |
1 |
32 x 0,20 |
2,4 |
2,9 |
0,6 |
1,5 |
19,5000 |
9,6 |
15 |
c.100 |
H07Z-K |
1,5 |
30 x 0,25 |
2,8 |
3,5 |
0,7 |
1,8 |
13,3000 |
14,4 |
24 |
c.100 |
2,5 |
50 x 0,25 |
3,4 |
4,3 |
0,8 |
2,6 |
7,9800 |
24,0 |
35 |
c.100 |
4 |
56 x 0,30 |
3,9 |
4,9 |
0,8 |
3,2 |
4,9500 |
38,4 |
51 |
c.100 |
6 |
84 x 0,30 |
4,4 |
5,5 |
0,8 |
3,9 |
3,3000 |
57,6 |
72 |
c.100 |
10 |
80 x 0,40 |
5,7 |
7,1 |
1,0 |
5,1 |
1,9100 |
96,0 |
120 |
c.100 |
16 |
128 x 0,40 |
6,7 |
8,4 |
1,0 |
6,3 |
1,2100 |
153,6 |
180 |
CUT |
25 |
200 x 0,40 |
8,4 |
10,6 |
1,2 |
7,8 |
0,7800 |
240,0 |
278 |
CUT |
35 |
280 x 0,40 |
9,7 |
12,1 |
1,2 |
9,2 |
0,5540 |
336,0 |
375 |
CUT |
50 |
400 x 0,40 |
11,5 |
14,4 |
1,4 |
11,0 |
0,3860 |
480,0 |
560 |
CUT |
70 |
356 x 0,50 |
13,2 |
16,6 |
1,4 |
13,1 |
0,2720 |
672,0 |
780 |
CUT |
95 |
485 x 0,50 |
15,2 |
18,8 |
1,6 |
15,0 |
0,2060 |
912,0 |
952 |
CUT |
120 |
614 x 0,50 |
16,7 |
20,9 |
1,6 |
17,0 |
0,1610 |
1152,0 |
1200 |
CUT |
150 |
765 x 0,50 |
18,6 |
23,3 |
1,8 |
19,0 |
0,1290 |
1440,0 |
1600 |
CUT |
185 |
944 x 0,50 |
20,6 |
25,8 |
2,0 |
21,0 |
0,1060 |
1776,0 |
2100 |
CUT |
240 |
1225 x 0,50 |
23,5 |
29,4 |
2,2 |
24,0 |
0,0801 |
2304,0 |
3015 |
CUT |
*) Packing: c.100 = coil 100 m CUT = cable in different lengths on drum or reel, possible cutting at required length