PP/R
PVC insulated and sheathed flat installation cable with detached cores
|
|
 |
 |
Application |
|
Cable for installation in dry rooms for permanent laying on or under plaster; without plaster in cavities of walls or ceilings made of incombustible construction materials. Simple fixing due to cable sheath spacing.
|
 |
Construction |
 |
Technical data |
Conductor: |
bare copper conductor, solid, class 1, acc. to IEC 60228 / HD 383 / DIN VDE 0295 |
Insulation: |
PVC compound PI1 acc. to HRN N.C0.195, parallelly laid cores separated by a wide groove in the sheath which enables provisional fixing of insulated conductor, colour marked cores acc. to HRN HD 308 S2 / DIN VDE 0293-308
|
Sheath: |
PVC compound |
sheath colour: |
white or black |
|
Core colour marking: |
HRN HD 308 S2 / VDE 0293-308 |
 |
Temperature range: |
|
during installationi: |
+5 °C up to +60 °C |
fixed installed: |
-30 °C up to +70 °C |
Nominal voltage: |
Uο/U = 380 V |
Test voltage: |
2000 V |
Minimal inner bending radius: |
4D
|
Behaviour in fire: |
IEC 60332-1 |
Dimensions – number of cores x conductor cross-section |
Construction of individual conductor |
External diameter |
Insulation thickness |
Sheath thickness |
Conductor resistance at 20 °C |
Specific. el. resistance of insulation at 70 °C
|
Cu weight |
Cable weight |
Packing*
|
|
nominal
|
min-max.
|
nominal
|
nominal
|
max.
|
min.
|
|
approx. |
|
mm²
|
n x mm
|
mm
|
mm
|
mm
|
Ω/km
|
MΩkm
|
kg/km
|
kg/km
|
|
2 x 1,5
|
1 x 1,36
|
11,5 x 4,0
|
0,6
|
0,6
|
12,2
|
0,010
|
28,8
|
70
|
c.100
|
2 x 2,5
|
1 x 1,75
|
14,0 x 4,5
|
0,7
|
0,7
|
7,56
|
0,009
|
48,0
|
103
|
c.100
|
2 x 4
|
1 x 2,23
|
15,2 x 5,6
|
0,8
|
0,7
|
4,70
|
0,008
|
76,8
|
140
|
c.100
|
|
3 x 1,5
|
1 x 1,36
|
15,5 x 4,0
|
0,6
|
0,6
|
12,2
|
0,010
|
43,2
|
102
|
c.100
|
3 x 2,5
|
1 x 1,75
|
18,2 x 4,5
|
0,7
|
0,7
|
7,56
|
0,009
|
72,0
|
152
|
c.100
|
3 x 4
|
1 x 2,23
|
20,6 x 5,6
|
0,8
|
0,7
|
4,70
|
0,008
|
115,2
|
203
|
c.100
|
*) Packing: c.100 = coil 100 m