JB-Y(St)Y
Fire alarm installation cable with PVC insulation and screen and Al-foil screen
|
alt. mark:
BMK
|
|
|
Application |
Standards |
|
Installation cable for transmission of fire alarm signals, for fixed installation within dry or damp premises, under or on plaster, also for fixed installation on external walls. Not for direct laying in ground or water, not intended for supply purposes. Electrostatic screen protects transmission circuits against external disturbing electromagnetic impacts.
|
DIN VDE 0815
|
|
Construction |
|
Technical data |
Conductor: |
bare solid copper conductor, of 0,8 mm diameter (cross-section 0,5 mm²) |
Insulation: |
PVC-compound of type YI1, acc. to DIN VDE 0207, of 0,2 mm or 0,4 mm thickness, per two conductors are twisted in pair, and pairs are stranded in layers, core colour marking is defined acc. to DIN VDE 0815 |
Separator: |
plastic tape |
Electrostatic screen: |
aluminium - laminated polyester tape and tinned copper contact conductor of 0,4 mm diameter for cables with up to 10 pairs, 0,6 mm for cables with more than 10 pairs |
Sheath: |
PVC-compound YM1 acc. to DIN VDE 0207 part 5, of thickness conforming with DIN VDE 0815 |
sheath colour: |
red (often with “BRANDMELDE” mark)
|
Temperature range: |
|
during application:
|
-5 °C up to +50 °C |
fixed installed: |
-30 °C up to +70 °C |
Operating voltage: |
max. 300 V |
Test voltage: |
|
core - core: |
800 V |
core - screen: |
800 V |
Insulation resistance: |
min. 100 MΩ/km |
Mutual capacitance: |
max. 1001) nF/km |
Capacitance unbalance: |
(at 800 Hz) max. 3002) pF/100m |
Loop resistance at 20 °C: |
max. 73,2 Ω/km |
Permitted current load: |
5,1 A |
Linear attenuation: |
(at 800 Hz) approx. 1,1 dB/km |
Min. inner bending radius: |
|
during laying or with repeated bending with stress: |
7,5D |
single bending without stress: |
2,5D |
Behaviour in fire: |
IEC 60332-1 |
Dimensions - number of
cores x conductor diameter |
External diameter |
Sheath thickness |
Cu weight |
Cable weight |
Packing* |
|
approx. |
nominal |
|
approx. |
|
N x mm² |
mm |
mm |
kg/km |
kg/km |
|
1 x 2 x 0,8 |
6,0 |
1,0 |
11 |
40 |
c.100, dr500 |
2 x 2 x 0,8 |
7,0 |
1,0 |
21 |
60 |
c.100, dr500 |
3 x 2 x 0,8 |
8,5 |
1,0 |
31 |
80 |
CUT |
4 x 2 x 0,8 |
9,0 |
1,0 |
41 |
100 |
CUT |
5 x 2 x 0,8 |
9,5 |
1,0 |
52 |
120 |
CUT |
6 x 2 x 0,8 |
10,5 |
1,0 |
62 |
140 |
CUT |
8 x 2 x 0,8 |
11,5 |
1,0 |
82 |
165 |
CUT |
10 x 2 x 0,8 |
13,0 |
1,2 |
102 |
210 |
CUT |
12 x 2 x 0,8 |
14,0 |
1,2 |
123 |
240 |
CUT |
14 x 2 x 0,8 |
14,5 |
1,2 |
144 |
275 |
CUT |
16 x 2 x 0,8 |
15,5 |
1,2 |
164 |
310 |
CUT |
20 x 2 x 0,8 |
16,5 |
1,2 |
204 |
380 |
CUT |
24 x 2 x 0,8 |
19,0 |
1,4 |
244 |
460 |
CUT |
30 x 2 x 0,8 |
20,0 |
1,4 |
304 |
550 |
CUT |
40 x 2 x 0,8 |
22,5 |
1,6 |
405 |
710 |
CUT |
50 x 2 x 0,8 |
25,5 |
1,6 |
506 |
880 |
CUT |
60 x 2 x 0,8 |
28,0 |
1,6 |
606 |
1040 |
CUT |
80 x 2 x 0,8 |
31,0 |
1,8 |
807 |
1400 |
CUT |
100 x 2 x 0,8 |
32,0 |
2,0 |
1008 |
1700 |
CUT |
*) Packing: c.100 = coil 100 m S500 = reel 500 m CUT = cable in different lengths on drum or reel, possible cutting at required length