H05V-U
PVC insulated conductor – single wire (solid)
|
JUS mark:
P
|
|
|
Application |
Standards |
|
Insulated conductor for internal wiring of electrical devices and lighting fixtures, i.e. as bridge junction. Laying in dry areas, in switchboards and distribution boards. In electrical-installation canal which can be opened, only for signaling and control circuits. Not for direct application under plaster.
|
HRN HD 21.3 S3
IEC 60227-3
DIN VDE 0281 part 3
|
|
Construction |
|
Technical data |
Conductor: |
bare copper conductor of class 1 (solid) acc, to IEC 60228 / HD 383 / DIN VDE 0295 |
Insulation: |
PVC compound TI1 acc. to IEC 60227-3 / HD 21.3 S3 / DIN VDE 00281 part 3 |
|
Conductor color identification: |
acc. to IEC 60446 i.e. EN 60446 (corresponding to DIN VDE 0293) |
possible insulation colors: |
|
Temperature range: |
|
during installation:
|
+5 °C up to+70 °C |
fixed installed: |
-30 °C up to+70 °C |
at short circuit of max. 5 s: |
up to 160 °C |
ambient temperature at storage: |
up to 40 °C |
Nominal voltage: |
Uο/U = 300/500 V |
Test voltage: |
2000 V |
Minimal inner bending radius: |
4D |
Behavior in fire: |
IEC 60332-1 |
Dimensions – conductor cross-section |
Construction of individual conductor |
External diameter |
Insulation thickness |
Conductor resistance at 20 °C |
Specific. el. resistance of insulation at 70°C |
Cu weight |
Cable weight |
Permitted stress |
Packing* |
|
nominal |
min-max. |
nominal |
max. |
min. |
|
approx. |
max. |
|
mm² |
n x mm |
mm |
mm |
Ω/km |
MΩkm |
kg/km |
kg/km |
N |
|
0,5 |
1 x 0,80 |
1,9 – 2,3 |
0,6 |
36,0 |
0,014 |
4,8 |
9 |
25 |
c.100 |
0,75 |
1 x 0,95 |
2,1 – 2,5 |
0,6 |
24,5 |
0,013 |
7,2 |
10 |
37,5 |
c.100 |
1 |
1 x 1,13 |
2,2 – 2,7 |
0,6 |
18,1 |
0,011 |
9,6 |
14 |
50 |
c.100 |
*) Packing: c.100 = coil 100 m