H05V-U

PVC insulated conductor – single wire (solid)

JUS mark: P

H05V-U
Primjena kabela

Application

Standards

 

Insulated conductor for internal wiring of electrical devices and lighting fixtures, i.e. as bridge junction. Laying in dry areas, in switchboards and distribution boards. In electrical-installation canal which can be opened, only for signaling and control circuits. Not for direct application under plaster.

HRN HD 21.3 S3
IEC 60227-3
DIN VDE 0281 part 3


Datasheet H05V-U 117.09 Kb

Konstrukcija kabela

Construction

Tehnički podaci kabela

Technical data

Conductor: bare copper conductor of class 1 (solid) acc, to IEC 60228 / HD 383 / DIN VDE 0295
Insulation: PVC compound TI1 acc. to IEC 60227-3 / HD 21.3 S3 / DIN VDE 00281 part 3
 
Conductor color identification: acc. to IEC 60446 i.e. EN 60446 (corresponding to DIN VDE 0293)
possible insulation colors: crna.jpg pro_bo.jpg plava.jpg
Temperature range:  
during installation:
+5 °C up to+70 °C
fixed installed: -30 °C up to+70 °C
at short circuit of max. 5 s: up to 160 °C
ambient temperature at storage: up to 40 °C
Nominal voltage: Uο/U = 300/500 V
Test voltage: 2000 V
Minimal inner bending radius: 4D
Behavior in fire: IEC 60332-1


Dimensions – conductor cross-section Construction of individual conductor External diameter Insulation thickness  Conductor resistance at 20 °C Specific. el. resistance of insulation at 70°C Cu weight Cable weight Permitted stress Packing*
  nominal min-max. nominal max. min.   approx. max.  
mm² n x mm mm mm Ω/km MΩkm kg/km kg/km N  
0,5 1 x 0,80 1,9 – 2,3 0,6 36,0 0,014 4,8 9 25 c.100
0,75 1 x 0,95 2,1 – 2,5 0,6 24,5 0,013 7,2 10 37,5 c.100
1 1 x 1,13 2,2 – 2,7 0,6 18,1 0,011 9,6 14 50 c.100

*) Packing: c.100 = coil 100 m


Products




Proizvodi