NA2XS2Y
Medium voltage single core cable 6/10 kV, 12/20 kV, 18/30 kV, XLPE insulated, PE sheath, with Al conductors and screen of Cu conductors
|
|
|
|
Application |
Standards |
|
Medium voltage power cable for static application in ground, within and outside facilities, outdoor, in cable canals, in dry areas or in water. PE sheath secures increased mechanical resistance during and after laying.
Due to its very low factor of dielectric loss, which remains constant over its entire operating lifetime, and owing to excellent insulation property of XLPE-material, firmly longitudinally spliced with inner and external screen of semi-conductive material (extruded in one process), the cable has a high operating reliability.
Used in transformer stations, switching blocks, in electric power plants and industrial plants. To avoid the effects of external impact, the adhering semi-conductive layer extruded between conductor and insulation, along with concentric copper conductor, secures restriction of electric field and resistance to partial discharges.
|
HRN HD 620 S1
IEC 60502-2
DIN VDE 0276 part 620
|
|
Construction |
|
Technical data |
Conductor: |
Al round conductor, multi wire stranded compacted(RM), class 2 acc. to HRN HD 383 / IEC 60228 / DIN VDE 0295 |
Inner screen: |
extruded semi-conductive skin on conductor |
Insulation: |
XLPE (cross-linked polyethylene, recent mark: PE-X) compound DIX 8 acc. to HRN HD 620 S1 |
External screen: |
extruded semi-conductive skin on insulation, longitudinally spliced with insulation
(+tape of semi-conductive material) |
Concentric conductor: |
in inner layer corrugated spirally wrapped copper wires, in external layer copper tape wrapped in counter-helix |
Separating |
tape |
Sheath: |
rigid PE (polyethylene) compound DMP 2 acc. to HRN HD 620 S1 |
sheath colour: |
black |
Temperature range: |
|
during installation:
|
-20 °C up to +70 °C |
max. operating temp.: |
+90 °C |
at short circuit of max. 5 s: |
up to 250 °C |
|
Minimal inner bending radius: |
15D |
Behaviour in fire: |
Halogen-free polyethylene sheath, but it is NOT self-extinguishing and fire-resistant acc. to IEC 60332-1 |
Dimensions – number of cores x conductor cross-section |
Construction |
External diameter |
External diameter |
Conductor diameter |
Insulation thickness |
Conductor resistance at20 °C |
Short circuit current 1s |
Cu weight |
Cable weight |
Packing* |
|
|
min. |
max. |
max. |
nom. |
max. |
nominal |
|
approx. |
|
N x mm²
|
|
mm |
mm |
mm |
mm |
Ω/km |
A |
kg/km |
kg/km |
|
6/10 kV |
1 x 50/16 |
RM |
24 |
29 |
8,6 |
3,4 |
0,641 |
4,7 |
182 |
650 |
CUT |
1 x 70/16 |
RM |
26 |
31 |
10,2 |
3,4 |
0,443 |
6,58 |
182 |
736 |
CUT |
1 x 95/16 |
RM |
27 |
32 |
12,0 |
3,4 |
0,32 |
8,93 |
182 |
852 |
CUT |
1 x 120/16 |
RM |
29 |
34 |
13,5 |
3,4 |
0,253 |
11,3 |
182 |
950 |
CUT |
1 x 150/16 |
RM |
30 |
35 |
15,0 |
3,4 |
0,206 |
14,1 |
182 |
1100 |
CUT |
1 x 150/25 |
RM |
30 |
35 |
15,0 |
3,4 |
0,206 |
14,1 |
283 |
1128 |
CUT |
1 x 185/16 |
RM |
32 |
37 |
16,8 |
3,4 |
0,164 |
17,4 |
182 |
1250 |
CUT |
1 x 185/25 |
RM |
32 |
37 |
16,8 |
3,4 |
0,164 |
17,4 |
283 |
1269 |
CUT |
1 x 240/16 |
RM |
34 |
39 |
19,2 |
3,4 |
0,125 |
22,6 |
182 |
1400 |
CUT |
1 x 240/25 |
RM |
34 |
39 |
19,2 |
3,4 |
0,125 |
22,6 |
283 |
1473 |
CUT |
1 x 300/25 |
RM |
36 |
41 |
21,6 |
3,4 |
0,1 |
28,2 |
283 |
1679 |
CUT |
1 x 400/35 |
RM |
40 |
45 |
24,6 |
3,4 |
0,0778 |
37,6 |
394 |
2076 |
CUT |
1 x 500/35 |
RM |
43 |
48 |
27,6 |
3,4 |
0,0605 |
47 |
394 |
2439 |
CUT |
12/20 kV |
1 x 50/16 |
RM |
28 |
33 |
8,6 |
5,5 |
0,641 |
4,7 |
182 |
806 |
CUT |
1 x 70/16 |
RM |
30 |
35 |
10,2 |
5,5 |
0,443 |
6,58 |
182 |
903 |
CUT |
1 x 95/16 |
RM |
31 |
36 |
12,0 |
5,5 |
0,32 |
8,93 |
182 |
1029 |
CUT |
1 x 120/16 |
RM |
33 |
38 |
13,5 |
5,5 |
0,253 |
11,3 |
182 |
1135 |
CUT |
1 x 150/16 |
RM |
34 |
39 |
15,0 |
5,5 |
0,206 |
14,1 |
182 |
1251 |
CUT |
1 x 150/25 |
RM |
34 |
39 |
15,0 |
5,5 |
0,206 |
14,1 |
283 |
1320 |
CUT |
1 x 185/16 |
RM |
36 |
41 |
16,8 |
5,5 |
0,164 |
17,4 |
182 |
1450 |
CUT |
1 x 185/25 |
RM |
36 |
41 |
16,8 |
5,5 |
0,164 |
17,4 |
283 |
1474 |
CUT |
1 x 240/16 |
RM |
39 |
44 |
19,2 |
5,5 |
0,125 |
22,6 |
182 |
1693 |
CUT |
1 x 240/25 |
RM |
39 |
44 |
19,2 |
5,5 |
0,125 |
22,6 |
283 |
1750 |
CUT |
1 x 300/25 |
RM |
41 |
46 |
21,6 |
5,5 |
0,1 |
28,2 |
283 |
1911 |
CUT |
1 x 400/35 |
RM |
44 |
49 |
24,6 |
5,5 |
0,0778 |
37,6 |
394 |
2330 |
CUT |
1 x 500/35 |
RM |
47 |
52 |
27,6 |
5,5 |
0,0605 |
47 |
394 |
2708 |
CUT |
1 x 630/35 |
RM |
50 |
55 |
29,3 |
5,5 |
0,0469 |
59,2 |
394 |
3177 |
CUT |
18/30 kV |
1 x 50/16 |
RM |
33 |
38 |
8,6 |
8,0 |
0,641 |
4,7 |
182 |
1036 |
CUT |
1 x 70/16 |
RM |
35 |
40 |
10,2 |
8,0 |
0,443 |
6,58 |
182 |
1146 |
CUT |
1 x 95/16 |
RM |
36 |
41 |
12,0 |
8,0 |
0,32 |
8,93 |
182 |
1286 |
CUT |
1 x 120/16 |
RM |
38 |
43 |
13,5 |
8,0 |
0,253 |
11,3 |
182 |
1404 |
CUT |
1 x 150/25 |
RM |
39 |
44 |
15,0 |
8,0 |
0,206 |
14,1 |
283 |
1598 |
CUT |
1 x 185/25 |
RM |
41 |
46 |
16,8 |
8,0 |
0,164 |
17,4 |
283 |
1776 |
CUT |
1 x 240/25 |
RM |
43 |
48 |
19,2 |
8,0 |
0,125 |
22,6 |
283 |
2004 |
CUT |
1 x 300/25 |
RM |
46 |
51 |
21,6 |
8,0 |
0,1 |
28,6 |
283 |
2300 |
CUT |
1 x 400/35 |
RM |
49 |
54 |
24,6 |
8,0 |
0,0778 |
37,6 |
394 |
2682 |
CUT |
1 x 500/35 |
RM |
52 |
57 |
27,6 |
8,0 |
0,0605 |
47 |
394 |
3150 |
CUT |
*) Packing: CUT = cable in different lengths on drum or reel, possible cutting at required length