SiHF

Silicone rubber insulated and sheathed flexible cable

harmonized mark: H05SS-F

SiHF
Application

Application

Standards

 

Silicone rubber is resistant to extreme temperature conditions, as for high (up to 180 °C, briefly even to 250 °C), so also for low (-60 °C) temperature. It has a high point (temperature) of inflammability, it is halogen-free, releases no corrosive gases at combustion, and around the conductor is formed additional insulation of silicone-oxide ashes. Due to a higher electrical resistance, tinned copper is also more suitable for higher temperatures (up to 220 °C) than bare copper. Such composition of these cables makes them applicable in extreme temperature environment, for inst. in steel production, aircraft industry, shipbuilding, cement plants and glass and ceramics factories, in electric power plants etc. They are also suitable for wiring of lighting, heating elements, burners, furnaces, saunas, solariums etc. To retain its mechanical properties at temperatures higher than 90 °C, silicone rubber needs to be properly ventilated or laid outdoor or in tubes. Due to low mechanical resistance and inclination to tearing, silicone rubber is not suitable for mobile application and significant bending and shifting during installation.

DIN VDE 0250 part 1
HRN HD 22.15 S1


Datasheet SiHF 117.09 Kb

Construction

Construction

Technical data

Technical data

Conductor: tinned copper conductor, fine wired stranded, class 5 acc. to IEC 60228 / HD 383 / DIN VDE 0295
Insulation: silicone rubber, concentrically stranded cores, colour marked acc. to DIN VDE 0293-308 / HD 308 S2, for 3 and more cores: with yellow-green protective core
Sheath: silicone rubber
sheath colour: red-brown
 
Core colour marking: acc. to HD 308 S2 / VDE 0293-308
SiHF
Temperature range:  
operating temp.:
-60 °C up to +180 °C
short-term peak temp.:
220 °C
Nominal voltage: Uο/U = 300/500 V
Test voltage: 2000 V
Breakdown voltage: 5000 V
Behaviour in fire: IEC 60332-1
Halogen-free: IEC 60754-1
Corrosiveness of combustion gases: not corrosive acc. to IEC 60754-2
Specific el. resistance of insulation: > 200 M Ω x km
Maximal tensile strength:  
under normal conditions: 5 N/mm²
after ageing (240h / 200°C): 4 N/mm²
Minimal inner bending radius: 15D
Permitted current load: at ambient temp. up to +145 ˚C acc. to DIN VDE 0100
when applied for higher temp.:  
SiHF


Dimensions – number of cores x conductor cross-section Construction of individual conductor External diameter Insulation
thickness
Sheath thickness Conductor resistance at 20 °C Cu weight Cable weight Packing*
  nominal nominal nominal nominal max.   approx.  
N x mm² n x mm mm mm mm Ω/km kg/km kg/km  
2 x 0,5 16 x 0,20 5,5 0,60 0,70 40,1 9,6 42 c.100
3 x 0,5 16 x 0,20 5,8 0,60 0,70 40,1 14,4 44 c.100
4 x 0,5 16 x 0,20 6,2 0,60 0,70 40,1 19,2 58 c.100
5 x 0,5 16 x 0,20 6,8 0,60 0,80 40,1 24 62 c.100
 
2 x 0,75 24 x 0,20 6,4 0,60 0,80 26,7 14,4 57 c.100
3 x 0,75 24 x 0,20 6,8 0,60 0,80 26,7 21,6 66 c.100
4 x 0,75 24 x 0,20 7,8 0,60 1,00 26,7 28,8 84 c.100
5 x 0,75 24 x 0,20 8,5 0,60 1,00 26,7 36 101 c.100
6 x 0,75 24 x 0,20 9,4 0,60 1,00 26,7 43,2 126 CUT
7 x 0,75 24 x 0,20 9,6 0,60 1,00 26,7 50,4 158 CUT
 
2 x 1 32 x 0,20 6,6 0,60 0,80 20,0 19,2 64 c.100
3 x 1 32 x 0,20 7,4 0,60 1,00 20,0 28,8 78 c.100
4 x 1 32 x 0,20 8,0 0,60 1,00 20,0 38,4 95 c.100
5 x 1 32 x 0,20 8,8 0,60 1,00 20,0 48 116 c.100
6 x 1 32 x 0,20 9,8 0,60 1,00 20,0 57,6 145 CUT
7 x 1 32 x 0,20 10,0 0,60 1,00 20,0 67,2 177 CUT
 
2 x 1,5 30 x 0,25 7,6 0,60 1,00 13,7 28,8 87 c.100
3 x 1,5 30 x 0,25 8,0 0,60 1,00 13,7 43,2 98 c.100
4 x 1,5 30 x 0,25 8,8 0,60 1,00 13,7 57,6 122 c.100
5 x 1,5 30 x 0,25 9,6 0,60 1,00 13,7 72 148 c.100
6 x 1,5 30 x 0,25 10,4 0,60 1,00 13,7 86,4 190 CUT
7 x 1,5 30 x 0,25 10,9 0,60 1,00 13,7 100,8 232 CUT
12 x 1,5 30 x 0,25 14,8     13,7 172,8 332 CUT
18 x 1,5 30 x 0,25 17,0     13,7 259,2 510 CUT
20 x 1,5 30 x 0,25 18,5     13,7 288 592 CUT
24 x 1,5 30 x 0,25 20,2     13,7 345,6 635 CUT
 
2 x 2,5 50 x 0,25 9,2 0,70 1,20 8,21 48 137 c.100
3 x 2,5 50 x 0,25 9,7 0,70 1,20 8,21 72 152 c.100
4 x 2,5 50 x 0,25 10,6 0,70 1,20 8,21 96 189 c.100
5 x 2,5 50 x 0,25 11,6 0,70 1,20 8,21 120 229 c.100
6 x 2,5 50 x 0,25 13,0 0,70 1,20 8,21 144 285 CUT
7 x 2,5 50 x 0,25 13,2 0,70 1,20 8,21 168 348 CUT
 
2 x 4 56 x 0,30 10,8 0,80 1,20 5,09 76,8 192 CUT
3 x 4 56 x 0,30 11,5 0,80 1,20 5,09 115,2 249 CUT
4 x 4 56 x 0,30 13,0 0,80 1,50 5,09 153,6 330 CUT
5 x 4 56 x 0,30 15,0 0,80 1,50 5,09 192 359 CUT
7 x 4 56 x 0,30 16,2 0,80   5,09 268,8 487 CUT
 
2 x 6 84 x 0,30 13,4 0,80 1,50 3,39 115,2 289 CUT
3 x 6 84 x 0,30 14,2 0,80 1,50 3,39 172,8 352 CUT
4 x 6 84 x 0,30 16,2 0,80 1,60 3,39 230,4 429 CUT
5 x 6 84 x 0,30 17,7 0,80 1,60 3,39 288 564 CUT
7 x 6 84 x 0,30 19,3 0,80   3,39 403,2 685 CUT
 
2 x 10 80 x 0,40 17,6 1,00 1,60 1,95 192 400 CUT
3 x 10 80 x 0,40 18,7 1,00 1,60 1,95 288 620 CUT
4 x 10 80 x 0,40 21,4 1,00 1,80 1,95 384 710 CUT
5 x 10 80 x 0,40 22,5 1,00 1,80 1,95 480 900 CUT
 
4 x 16 128 x 0,40 24,0     1,24 614,4 1014 CUT
5 x 16 128 x 0,40 26,5     1,24 768 1206 CUT
 
4 x 25 200 x 0,40 29,3     0,795 960 1460 CUT
 
4 x 35 280 x 0,40 31,0     0,565 1344 2146 CUT
5 x 35 280 x 0,40 34,2     0,565 1680 2650 CUT
 
4 x 50 400 x 0,40 34,7     0,393 1920 2990 CUT

*) Packing: c.100 = coil 100 m CUT = cable in different lengths on drum or reel, possible cutting at required length