H05V-U
PVC insulated conductor – single wire (solid)
|
JUS mark:
P
|
 |
 |
Application |
Standards |
| |
Insulated conductor for internal wiring of electrical devices and lighting fixtures, i.e. as bridge junction. Laying in dry areas, in switchboards and distribution boards. In electrical-installation canal which can be opened, only for signaling and control circuits. Not for direct application under plaster.
|
HRN HD 21.3 S3
IEC 60227-3
DIN VDE 0281 part 3
|
 |
Construction |
 |
Technical data |
| Conductor: |
bare copper conductor of class 1 (solid) acc, to IEC 60228 / HD 383 / DIN VDE 0295 |
| Insulation: |
PVC compound TI1 acc. to IEC 60227-3 / HD 21.3 S3 / DIN VDE 00281 part 3 |
| |
| Conductor color identification: |
acc. to IEC 60446 i.e. EN 60446 (corresponding to DIN VDE 0293) |
| possible insulation colors: |
 |
| Temperature range: |
|
during installation:
|
+5 °C up to+70 °C |
| fixed installed: |
-30 °C up to+70 °C |
| at short circuit of max. 5 s: |
up to 160 °C |
| okolna temperatura pri
skladištenju: |
up to 40 °C |
| Nominal voltage: |
Uο/U = 300/500 V |
| Test voltage: |
2000 V |
| Minimal inner bending radius: |
4D |
| Behavior in fire: |
IEC 60332-1 |
| Dimensions – conductor cross-section |
Construction of individual conductor |
External diameter |
Insulation thickness |
Conductor resistance at 20 °C
|
Specific. el. resistance of insulation at 70°C
|
Cu weight |
Cable weight |
Permitted stress |
Packing* |
| |
nominal |
min-max.
|
nominal |
max.
|
min.
|
|
approx. |
max.
|
|
|
mm²
|
n x mm
|
mm
|
mm
|
Ω/km
|
MΩkm
|
kg/km
|
kg/km
|
N
|
|
|
0,5
|
1 x 0,80
|
1,9 – 2,3
|
0,6
|
36,0
|
0,014
|
4,8
|
9
|
25
|
c.100
|
|
0,75
|
1 x 0,95
|
2,1 – 2,5
|
0,6
|
24,5
|
0,013
|
7,2
|
10
|
37,5
|
c.100
|
|
1
|
1 x 1,13
|
2,2 – 2,7
|
0,6
|
18,1
|
0,011
|
9,6
|
14
|
50
|
c.100
|
*) Packing: c.100 = coil 100 m