NAYCWY

Power cable 0,6/1 kV, PVC insulated and sheathed, with Al conductors and concentric protective corrugated Cu conductor

JUS mark: PP40-A

NAYCWY
Application

Application

Standards

 

Distribution power cable for static outdoor application (with protection against direct UV-irradiation), in ground, in water, within facilities, in cable canals, in concrete, in conditions where there is a danger of possible mechanical damages, but where the cable is not exposed either to systematic mechanical stress or heavier tensile strain. Used in electric power plants, transformer stations, industrial plants, metropolitan networks and other electric plants. Concentric conductor can be used as neutral, protective or earth connection, and in situations where the insulation might be roughly damaged by some metal object, it acts as protection against contact voltage. Corrugated, concentric conductor construction enables establishing of several cable connections without cutting of conductor.

HRN HD 603 S1
IEC 60502-1
DIN VDE 0276 part 603


Datasheet NAYCWY 117.09 Kb

Construction

Construction

Technical data

Technical data

Conductor: Al, class 1 or 2 acc. to HRN HD 383 / IEC 60228 / DIN VDE 0295
class 1: solid, round (RE)
class 2: multi wire stranded, round (RM) or sector (SM)
Insulation: PVC compound DIV-4 acc. to HRN HD 603.1, concentrically stranded cores, colour marked acc. to HRN HD 308 S2 / VDE 0293-308, without protective yellow-green conductor
Concentric conductor: in inner layer round copper wires, in external layer copper tape wrapped in counter-helix
Filler: extruded elastomer or plastomer compound or wrapped thermoplastic tapes
Sheath: PVC compound DMV-5 acc. to HRN HD 603.1
sheath colour: black
Izvedba.jpg
 
Core colour marking: HRN HD 308 S2 / VDE 0293-308
NYMboja.jpg
Temperature range:  
during installation:
-5 °C up to +50 °C
fixed installed: -30 °C up to +70 °C
at short circuit of max. 5 s: up to 160 °C
Nominal voltage: Uο/U = 0,6/1 kV
Test voltage: 4 kV
Max. operating voltage in three-phase systems: 1,2 kV
Maximal tensile strength: 30 N/mm²
Behaviour in fire: IEC 60332-1
Minimal inner bending radius:  
single core: 15D
multi core: 12D


Dimensions – number of cores x conductor cross-section Construction External diameter Insulation thickness Sheath thickness Conductor resistance at 20 °C Short circuit current 1s Cu weight Cable weight Packing*
    min-max. nom. nominal max. nominal   approx.  
N x mm²   mm mm mm Ω/km kA kg/km kg/km  
3 x 35/35 SM 26 - 31 1,2 1,8 0,868 2,6 240 1300 CUT
3 x 50/50 SM 27 - 33 1,4 1,8 0,641 3,8 340 1400 CUT
3 x 70/70 SM 31 - 37 1,4 2,0 0,443 5,3 475 1950 CUT
3 x 95/95 SM 35 - 42 1,6 2,2 0,320 7,2 640 2500 CUT
3 x 120/120 SM 38 - 45 1,6 2,3 0,253 9,1 800 2950 CUT
3 x 150/150 SM 42 - 49 1,8 2,4 0,206 11,4 1000 3550 CUT
3 x 185/185 SM 47 - 54 2,0 2,6 0,164 14,1 1230 4300 CUT
 
4 x 25/16 RE - 1,2 1,8 1,200 1,9 182 1150 CUT
4 x 35/16 RM - 1,2 1,8 0,868 2,6 182 1200 CUT
4 x 50/25 SM - 1,4 1,8 0,641 3,8 283 1600 CUT
4 x 70/35 SM - 1,4 2,0 0,443 5,3 394 2250 CUT
4 x 95/50 SM - 1,6 2,2 0,320 7,2 560 2900 CUT
4 x 120/70 SM - 1,6 2,3 0,253 9,1 780 3500 CUT
4 x 150/70 SM - 1,8 2,4 0,206 11,4 780 4200 CUT
4 x 185/95 SM - 2,0 2,6 0,164 14,1 1055 4950 CUT
4 x 240/120 SM - 2,2 2,9 0,125 18,2 1330 5600 CUT

*) Packing: CUT = cable in different lengths on drum or reel, possible cutting at required length