JB-H(St)H

Halogen-free fire alarm installation cable, with improved properties under fire

 
JB-H(St)H
Application

Application

Standards

 

Halogen-free installation cable for transmission of fire alarm signals, with improved properties under fire. Electrostatic screen protects transmission circuits against external disturbing electromagnetic impacts. Suitable for fixed installation in dry or damp premises where people and material goods need to be protected in case of fire. Recommended for public and industrial facilities where a lot of people is gathering, and for facilities of high material value. Not for direct laying in ground or water, not for outdoor application (except when adequately protected against sunlight), not intended for supply purposes.

advantages:
- halogen-free, no release of toxic and corrosive gases under fire
- reduced smoke manifestation under fire
- no flame propagation in vertical cable bundle , flame retardant

DIN VDE 0815


Datasheet JB-H(St)H

Construction

Construction

Construction

Technical data

Conductor: bare solid copper conductor, of 0,8 mm diameter
Insulation: halogen-free polyolefin compound HI2, acc. to DIN VDE 0207 part 23, of 0,3 or 0,4 mm thickness, per four conductors are stranded in star-quad, each 5 quads are stranded in bundle, and bundles are stranded in layers , core colour marking is defined acc. to DIN VDE 0815
Separator: PEPT - plastic tape of poly (ethylene/propylene) or polyester tape
Electrostatic screen: aluminium - laminated polyester tape and tinned copper contact conductor of 0,6 or 0,8 mm diameter
Sheath: halogen-free polyolefin compound HM2 acc. to DIN VDE 0207 part 24
sheath colour: red
Temperature range:  
during installation:
-5 °C up to +50 °C
fixed installed: -30 °C up to +70 °C
Operating voltage: max. 300 V
Test voltage:  
core - core: 800 V
core - screen: 800 V
Insulation resistance: min. 100 MΩxkm
Mutual capacitance: (at 800 Hz) max. 300 pF/100m
Loop resistance at 20°C: max. 73,2 Ω/km
Current load: 5,1 A
Linear attenuation: (at 800 Hz) approx. 1,1 dB/km
Min. inner bending radius:  
during laying or with repeated bending with stress: 7,5D
single bending without stress: 2,5D
Flame retardant: IEC 60332-1
No flame propagation in vertical cable bundle: IEC 60332-3
Halogen-free: IEC 60754-1
Non-corrosive combustion gases: IEC 60754-2
Low smoke density: IEC 61034-2


Dimensions - number of
cores x conductor diamter
External diameter Fire load Cu weight Cable weight Packing*
  approx.     approx.  
N x mm² mm kWh/m kg/km kg/km  
2 x 2 x 0,8 7,0 0,22 25 69 CUT
4 x 2 x 0,8 9,0 0,37 45 136 CUT
6 x 2 x 0,8 10,5 0,43 65 152 CUT
10 x 2 x 0,8 13,0 0,60 106 230 CUT
20 x 2 x 0,8 16,5 0,95 206 508 CUT
30 x 2 x 0,8 20,0 1,38 307 599 CUT
40 x 2 x 0,8 22,5 1,73 407 787 CUT
50 x 2 x 0,8 25,5 2,05 508 973 CUT
60 x 2 x 0,8 28,0 2,48 608 1121 CUT
80 x 2 x 0,8 31,0 3,14 809 1476 CUT
100 x 2 x 0,8 32,0 3,91 1010 1805 CUT

*) Packing: CUT = cable in different lengths on drum or reel, possible cutting at required length