H1Z2Z2-K

Single core flexible cable, suited for photovoltaic and solar systems, up to 1,8kV, special HEPR insulated

 
H1Z2Z2-K
Primjena kabela

Application

Standards

 

Single core flexible cables suited for photovoltaic and solar system with cross-linked polymer insulation and halogen free sheath. Tested for more 25 years lifetime. These cables can be used up 1800V to earth. Cable suitable for the interconnection of the various elements of photovoltaic systems, suitable for fixed installations outside and indoor, unprotected pipes. For direct, or indirect under- ground wiring.

additional features:
- ozone-resistant according to EN50396
- UV-resistant according to HD605/A1
- the cable is tested for durability according to EN 60216 (indicated also in 2P fg 169/08.2007)

standard interpretation under:
- continuous use temperature 120°C for 20000h (= 2.3, years)
- continuous use temperature 90°C (= 30 years )

IEC 60332-1-2
EN 50267-1-2
EN 50267-2-2
EN 60216
TÜV


Datasheet H1Z2Z2-K

Construction

Construction

Technical data

Technical data

Conductor: tinned fine wired copper conductor, class 5, acc. to EN 60228
Insulation: HEPR 120°C similar to IEC 60502-1
(type EI6/ EI8)
Sheath: crossed linked compound M21
sheath colour: black
 
Core colour identification: natural colour - bright
Temperature range:  
fixed installed: -40 °C up to +90 °C
min. cable temp. at bending/installation: -40 °C
max. operating temp.: +120 °C
at short circuit of max. 5 s: up to 250 °C
Nominal voltage AC: Uο/U = 0,7/1,2 kV
Nominal voltage DC: Uο/U = 0,9/1,8 kV
Test voltage AC: 6 kV
Test voltage DC: 10 kV
Max. tensile strength of Cu conductor:  
during operation: 15 N/m²
during installation: 15 N/m²
Min. inner bending radius: 4D
Properties under fire:  
Flame retardant: IEC 60332-1
No flame propagation in vertical cable bundle: IEC 60332-3
Halogen-free: IEC 60754-1
Non-corrosive combustion gases: IEC 60754-2
Low smoke density: IEC 61034-2


Dimensions - number of cores x conductor cross-section Construction of individual conductor External diameter Conductor diameter Insulation thickness Conductor resistance at 20 °C Current load Cu weight Cable weight Packing*
nominal nominal approx. nominal nominal max. nominal   approx.  
N x mm² n x mm mm mm mm mm Ω/km kg/km kg/km  
1 x 1,5 30 x 0,25 5,1 1,6 0,7 13,3 30 14,4 38,4 CUT
1 x 2,5 50 x 0,25 5,4 2,0 0,7 7,98 41 24 45,4 CUT
1 x 4 56 x 0,30 6,2 2,5 0,7 4,95 55 38,4 60,1 CUT
1 x 6 84 x 0,30 6,9 3,1 0,7 3,30 70 57,6 90,7 CUT
1 x 10 80 x 0,40 8,2 4,1 0,7 1,91 98 96 131,1 CUT
1 x 16 128 x 0,40 9,3 5,2 0,7 1,21 132 153,6 187,1 CUT
1 x 25 200 x 0,40 10,8 6,5 0,9 0,78 176 240 276,1 CUT
1 x 35 280 x 0,40 12,1 7,5 0,9 0,554 218 336 368,8 CUT
1 x 50 400 x 0,40 14,8 9,0 1,0 0,386 276 480 557 CUT
1 x 70 356 x 0,50 16,9 11,0 1,1 0,272 347 672 767 CUT
1 x 95 485 x 0,50 18,7 12,7 1,1 0,206 416 912 989,6 CUT
1 x 120 614 x 0,50 20,7 13,7 1,2 0,161 488 1152 1232,8 CUT

*) Packing: CUT = cable in different lengths on drum or reel, possible cutting at required length