N2XS(F)2Y

Medium voltage single core cable 6/10 kV, 12/20 kV, 18/30 kV, XLPE insulated, PE sheathed, with screen of Cu conductors, longitudinally watertight

JUS mark: XHE49

N2XS(F)2Y
Application

Application

Standards

 

Medium voltage power cable for static application in ground, within and outside facilities, outdoor, in cable canals, in dry areas or in water. PE sheath secures increased mechanical resistance during and after laying. Swellable tape blocks water spreading within the cable. Due to its very low factor of dielectric loss, which remains constant over its entire operating lifetime, and owing to excellent insulation property of XLPE-material, firmly longitudinally spliced with inner and external screen of semi-conductive material (extruded in one process), the cable has a high operating reliability. Used in transformer stations, switching blocks, in electric power plants and industrial plants. To avoid the effects of external impact, the adhering semi-conductive layer extruded between conductor and insulation, along with concentric copper conductor, secures restriction of electric field and resistance to partial discharges.

HRN HD 620 S1
IEC 60502-2
DIN VDE 0276 part 620


Datasheet N2XS(F)2Y 117.09 Kb

Construction

Construction

Technical data

Technical data

Conductor: Cu round conductor, multi wire stranded compacted (RM), class 2 acc. to HRN HD 383 / IEC 60228 / DIN VDE 0295
Inner screen: extruded semi-conductive skin on conductor
Insulation: XLPE (cross-linked polyethylene, recent mark: PE-X) compound DIX 8 acc. to HRN HD 620 S1
External screen: extruded semi-conductive skin on insulation, longitudinally spliced with insulation (+tape of semi-conductive material)
Swellable tape: watertight, semi-conductive
Concentric conductor: in inner layer corrugated spirally wrapped copper wires, in external layer copper tape wrapped in counter-helix
Separating tape
Sheath: rigid PE (polyethylene) compound DMP 2 acc. to HRN HD 620 S1
sheath colour: black
Temperature range:  
during installation:
-20 °C up to +70 °C
max. operating temp.: +90 °C
at short circuit of max. 5 s: up to 250 °C
NYMboja.jpg
Minimal inner bending radius: 15D
Behaviour in fire: Halogen-free polyethylene sheath, but it is NOT self-extinguishing and fire-resistant acc. to IEC 60332-1


Dimensions – number of cores x conductor cross-section Construction External diameter External diameter Conductor diameter Insulation thickness Conductor resistance at 20 °C Short circuit current 1s Cu weight Cable weight Packing*
    min. max. max. nominal max. nominal   approx.  
N x mm²   mm mm mm mm Ω/km A kg/km kg/km  
6/10 kV
1 x 35/16 RM 23 28 7,5 3,4 0,524 5,00 518   CUT
1 x 50/16 RM 24 29 8,6 3,4 0,387 7,15 662 934 CUT
1 x 70/16 RM 26 31 10,2 3,4 0,268 10,0 854 1154 CUT
1 x 95/16 RM 27 32 12,0 3,4 0,193 13,6 1094 1418 CUT
1 x 120/16 RM 29 34 13,5 3,4 0,153 17,2 1334 1660 CUT
1 x 150/25 RM 30 35 15,0 3,4 0,124 21,4 1723 2016 CUT
1 x 185/25 RM 32 37 16,8 3,4 0,0991 26,5 2059 2357 CUT
1 x 240/25 RM 34 39 19,2 3,4 0,0754 34,3 2587 2911 CUT
1 x 300/25 RM 36 41 21,6 3,4 0,0601 42,9 3163   CUT
1 x 400/35 RM 40 45 24,6 3,4 0,0470 57,2 4234   CUT
1 x 500/35 RM 43 48 27,6 3,4 0,0366 71,5 5194   CUT
12/20 kV
1 x 35/16 RM 27 32 7,5 5,5 0,524 5,00 518   CUT
1 x 50/16 RM 28 33 8,6 5,5 0,387 7,15 662 1091 CUT
1 x 70/16 RM 30 35 10,2 5,5 0,268 10,0 854 1322 CUT
1 x 95/16 RM 31 36 12,0 5,5 0,193 13,6 1094 1596 CUT
1 x 120/16 RM 33 38 13,5 5,5 0,153 17,2 1334 1847 CUT
1 x 150/25 RM 34 39 15,0 5,5 0,124 21,4 1723 2212 CUT
1 x 185/25 RM 36 41 16,8 5,5 0,0991 26,5 2059 2564 CUT
1 x 240/25 RM 39 44 19,2 5,5 0,0754 34,3 2587 3132 CUT
1 x 300/25 RM 41 46 21,6 5,5 0,0601 42,9 3163 3722 CUT
1 x 400/35 RM 44 49 24,6 5,5 0,0470 57,2 4234 4639 CUT
1 x 500/35 RM 47 52 27,6 5,5 0,0366 71,5 5194 5670 CUT
18/30 kV
1 x 50/16 RM 33 38 8,6 8,0 0,387 7,15 662 1312 CUT
1 x 70/16 RM 35 40 10,2 8,0 0,268 10,0 854 1555 CUT
1 x 95/16 RM 36 41 12,0 8,0 0,193 13,6 1094 1842 CUT
1 x 120/16 RM 38 43 13,5 8,0 0,153 17,2 1334 2104 CUT
1 x 150/25 RM 39 44 15,0 8,0 0,124 21,4 1723 2478 CUT
1 x 185/25 RM 41 46 16,8 8,0 0,0991 26,5 2059 2843 CUT
1 x 240/25 RM 43 48 19,2 8,0 0,0754 34,3 2587 3428 CUT
1 x 300/25 RM 46 51 21,6 8,0 0,0601 42,9 3163   CUT
1 x 400/35 RM 49 54 24,6 8,0 0,0470 57,2 4234   CUT
1 x 500/35 RM 52 57 27,6 8,0 0,0366 71,5 5194   CUT

*) Packing: CUT = cable in different lengths on drum or reel, possible cutting at required length


Products