RE-2Y(St)Y

Instrumentation cable, PE insulated, with common screen, PVC sheathed

Similar cables: EP47

RE-2Y(St)Y
Application

Application

Standards

 

Cable with protective screen against electromagnetic impacts, for reliable and quick (up to 200 kB/s) transmission of analogue and digital signals, suitable for fixed and mobile installations in process control and data processing systems, mostly in chemical and petrochemical industrial plants and electric power plants. Low values of signal attenuation and low mutual capacitance enable large-distance signal transmission. Laid in dry and damp premises, also outdoor, in air or ground. Not intended for supply purposes.

EN 50288-7
DIN VDE 819-7


Datasheet RE-2Y(St)Y

Construction

Construction

Construction

Technical data

Conductor: bare copper conductor, multi wire stranded, class 2 acc. to IEC 60228 / HD 383 / DIN VDE 0295
Insulation: construction 2Y - PE-compound acc. to EN 50290-2-23; construction 2X - PE-X (cross-linked polyethylene) compound acc. to EN 50290-2-29, conductors twisted in pairs, pairs stranded in layers
core colour marking:
a-core: black
b-core: white with black numbers 1|1, 2|2,..
additional conductor: 0,5 mm² cross-section, orange coloured insulation (at multi core cables)
Separator: transparent plastic foil
Electrostatic screen: aluminium - laminated polyester tape and copper contact multi wire conductor of nominal cross-section 0,5 mm² (7 x 0,3 mm)
Sheath: acc. to EN 50290-2-22: construction 2Y - PVC compound; construction 2X - PVC compound for 90°C
sheath colour: blue (RAL 5015) or black
Temperature range:  
during installation:
-5 °C up to +50 °C
fixed installed (construction 2Y): -30 °C up to +70 °C
fixed installed (construction 2X): -30 °C up to +90 °C
Nominal voltage: 300 V
Test voltage:  
core - core: 1500 V
core - screen: 1500 V
Insulation resistance: min. 5 GΩ x km
Capacitance unbalance (at 1 kHz): 500 pF/500m
Inductance: 0,75 mH/km
Crosstalk attenuation (at 60 kHz): min. 0,85 dB/km
Min. inner bending radius: 7,5D
Behaviour in fire: IEC 60332-1

 


Dimensions - nominal cross-section Dimensions - number of cores x conductor diameter External diameter Insulation thickness Conductor resistance at 20°C Mutual capacitance Ratio   L / R Cu weight Cable weight Packing*
  nominal approx. nominal max. max. max.   approx.  
N x mm² n x mm mm mm Ω/km pF/m µH/Ω kg/km kg/km  
1 x 2 x 0,50 7 x 0,30 5,4 0,40 36,7 115 25 14 35 CUT
2 x 2 x 0,50 7 x 0,30 7,9 0,40 36,7 115 25 24 60 CUT
4 x 2 x 0,50 7 x 0,30 9,4 0,40 36,7 115 25 43 95 CUT
5 x 2 x 0,50 7 x 0,30 9,9 0,40 36,7 90 25 53 110 CUT
6 x 2 x 0,50 7 x 0,30 10,6 0,40 36,7 90 25 62 125 CUT
8 x 2 x 0,50 7 x 0,30 12 0,40 36,7 90 25 82 165 CUT
10 x 2 x 0,50 7 x 0,30 13,1 0,40 36,7 90 25 101 195 CUT
12 x 2 x 0,50 7 x 0,30 14,3 0,40 36,7 90 25 120 230 CUT
16 x 2 x 0,50 7 x 0,30 16,1 0,40 36,7 90 25 158 295 CUT
20 x 2 x 0,50 7 x 0,30 17,9 0,40 36,7 90 25 197 360 CUT
24 x 2 x 0,50 7 x 0,30 19,3 0,40 36,7 90 25 235 420 CUT
 
1 x 2 x 0,75 7 x 0,37 6 0,40 25 115 25 19 45 CUT
2 x 2 x 0,75 7 x 0,37 8,8 0,40 25 115 25 34 75 CUT
4 x 2 x 0,75 7 x 0,37 10,2 0,40 25 115 25 62 120 CUT
5 x 2 x 0,75 7 x 0,37 10,9 0,40 25 90 25 77 145 CUT
6 x 2 x 0,75 7 x 0,37 11,7 0,40 25 90 25 91 170 CUT
8 x 2 x 0,75 7 x 0,37 13,1 0,40 25 90 25 120 210 CUT
10 x 2 x 0,75 7 x 0,37 14,6 0,40 25 90 25 149 260 CUT
12 x 2 x 0,75 7 x 0,37 15,7 0,40 25 90 25 178 300 CUT
16 x 2 x 0,75 7 x 0,37 17,9 0,40 25 90 25 235 395 CUT
20 x 2 x 0,75 7 x 0,37 19,9 0,40 25 90 25 293 485 CUT
24 x 2 x 0,75 7 x 0,37 21,4 0,40 25 90 25 350 565 CUT
 
1 x 2 x 1 7 x 0,43 6,4 0,40 18,5 115 25 24 50 CUT
2 x 2 x 1 7 x 0,43 9,5 0,40 18,5 115 25 43 90 CUT
4 x 2 x 1 7 x 0,43 11,1 0,40 18,5 115 25 82 145 CUT
5 x 2 x 1 7 x 0,43 11,8 0,40 18,5 90 25 101 175 CUT
6 x 2 x 1 7 x 0,43 12,7 0,40 18,5 90 25 120 205 CUT
8 x 2 x 1 7 x 0,43 14,4 0,40 18,5 90 25 158 265 CUT
10 x 2 x 1 7 x 0,43 15,8 0,40 18,5 90 25 197 320 CUT
12 x 2 x 1 7 x 0,43 17,3 0,40 18,5 90 25 235 380 CUT
16 x 2 x 1 7 x 0,43 19,7 0,40 18,5 90 25 312 495 CUT
20 x 2 x 1 7 x 0,43 21,6 0,40 18,5 90 25 389 605 CUT
24 x 2 x 1 7 x 0,43 23,6 0,40 18,5 90 25 466 720 CUT
 
1 x 2 x 1,3 7 x 0,49 7 0,45 14,2 120 40 30 60 CUT
2 x 2 x 1,3 7 x 0,49 10,5 0,45 14,2 120 40 55 15 CUT
4 x 2 x 1,3 7 x 0,49 12,5 0,45 14,2 120 40 15 185 CUT
5 x 2 x 1,3 7 x 0,49 13,1 0,45 14,2 15 40 130 215 CUT
6 x 2 x 1,3 7 x 0,49 14,3 0,45 14,2 15 40 155 260 CUT
8 x 2 x 1,3 7 x 0,49 16,1 0,45 14,2 15 40 204 330 CUT
10 x 2 x 1,3 7 x 0,49 17,9 0,45 14,2 15 40 254 405 CUT
12 x 2 x 1,3 7 x 0,49 19,5 0,45 14,2 15 40 304 485 CUT
16 x 2 x 1,3 7 x 0,49 22,2 0,45 14,2 15 40 404 635 CUT
20 x 2 x 1,3 7 x 0,49 24,4 0,45 14,2 15 40 504 770 CUT
24 x 2 x 1,3 7 x 0,49 26,6 0,45 14,2 15 40 604 920 CUT
 
1 x 2 x 1,5 7 x 0,52 7,2 0,45 12,3 120 40 34 65 CUT
2 x 2 x 1,5 7 x 0,52 10,8 0,45 12,3 120 40 62 110 CUT
4 x 2 x 1,5 7 x 0,52 12,9 0,45 12,3 120 40 120 200 CUT
5 x 2 x 1,5 7 x 0,52 13,6 0,45 12,3 15 40 149 240 CUT
6 x 2 x 1,5 7 x 0,52 14,8 0,45 12,3 15 40 178 285 CUT
8 x 2 x 1,5 7 x 0,52 16,9 0,45 12,3 15 40 235 375 CUT
10 x 2 x 1,5 7 x 0,52 18,5 0,45 12,3 15 40 293 450 CUT
12 x 2 x 1,5 7 x 0,52 20,2 0,45 12,3 15 40 350 540 CUT
16 x 2 x 1,5 7 x 0,52 23 0,45 12,3 15 40 466 705 CUT
20 x 2 x 1,5 7 x 0,52 25,5 0,45 12,3 15 40 581 870 CUT
24 x 2 x 1,5 7 x 0,52 27,8 0,45 12,3 15 40 696 1035 CUT

*) Packing: CUT = cable in different lengths on drum or reel, possible cutting at required length