JE-LiYCY

Flexible cable for data transmission in industrial electronics, PVC insulated and sheathed, with Cu braid

 
JE-LiYCY
Application

Application

Standards

 

Flexible cable with protective screen against electromagnetic impacts, for transmission of analogue and digital signals, suitable for fixed and mobile installations in device production, for electronic, computer and measurement systems, in mobile and production conveyers, for office devices. Usage with shifting is only possible if not exposed to stress and mechanical loads. Laid in dry and damp premises, but outdoor application is not recommended, except in special cases under protection against direct sunlight. Not for direct laying in ground or water, not intended for supply purposes.

DIN VDE 0812


Datasheet JE-LiYCY

Construction

Construction

Construction

Technical data

Conductor: bare copper conductor, multi wire stranded, of cross-section 0,5 mm², class 2 acc. to IEC 60228 / HD 383 / DIN VDE 0295 (number of wires in cross-section: 7 x 0,3 mm)
Insulation: PVC-compound of type YI3, acc. to DIN VDE 0207 part 4, conductors twisted in pairs, per 4 pairs are stranded in bundle, bundles are stranded in layers
Separator: transparent plastic foil
Electrostatic screen: braid of tinned copper wires of 0,2 mm thickness, with approx. 85% overlap
Sheath: PVC-compound YM1 acc. to DIN VDE 0207 part 5
sheath colour: grey (RAL 7032) or blue (RAL 5015)
Temperature range:  
during installation:
-5 °C up to +70 °C
fixed installed: -30 °C up to +70 °C
Nominal voltage: 225 V
Test voltage:  
core - core: 500 V
core - screen: 2000 V
Insulation resistance: min. 100 MΩ x km
Mutual capacitance(at 800 Hz): max. 1001) nF/km
Capacitance unbalance(at 800 Hz): max. 200 pF/100m
Loop resistance at 20°C: max. 73,2 Ω/km
Inductance: 0,65 mH/km
Permitted current load: 5,1 A
Linear attenuation(at 800 Hz): about 1,1 dB/km
Min. inner bending radius:  
during laying or with repeated bending with stress: 10D
single bending without stress: 5D
Behaviour in fire: IEC 60332-1

 


Dimensions - nominal cross-section Dimensions - number of cores x conductor diameter Sheath thickness External diameter Conductor resistance at 20 °C Cu weight Cable weight Packing*
  nominal nominal approx. max.   approx.  
N x mm² n x mm mm mm Ω/km kg/km kg/km  
2 x 2 x 0,5 16 x 0,20 1 7,5 39 48 81 CUT
4 x 2 x 0,5 16 x 0,20 1 10 39 84 137 CUT
8 x 2 x 0,5 16 x 0,20 1 13 39 140 248 CUT
12 x 2 x 0,5 16 x 0,20 1,2 15,5 39 193 307 CUT
16 x 2 x 0,5 16 x 0,20 1,2 17 39 243 375 CUT
20 x 2 x 0,5 16 x 0,20 1,2 18,5 39 292 461 CUT
24 x 2 x 0,5 16 x 0,20 1,4 20,5 39 342 595 CUT
32 x 2 x 0,5 16 x 0,20 1,4 22,5 39 435 719 CUT
40 x 2 x 0,5 16 x 0,20 1,4 24 39 531 831 CUT

*) Packing: CUT = cable in different lengths on drum or reel, possible cutting at required length