NA2XS2Y

Medium voltage single core cable 6/10 kV, 12/20 kV, 18/30 kV, XLPE insulated, PE sheath, with Al conductors and screen of Cu conductors

 
NA2XS2Y
Application

Application

Standards

 

Medium voltage power cable for static application in ground, within and outside facilities, outdoor, in cable canals, in dry areas or in water. PE sheath secures increased mechanical resistance during and after laying. Due to its very low factor of dielectric loss, which remains constant over its entire operating lifetime, and owing to excellent insulation property of XLPE-material, firmly longitudinally spliced with inner and external screen of semi-conductive material (extruded in one process), the cable has a high operating reliability. Used in transformer stations, switching blocks, in electric power plants and industrial plants. To avoid the effects of external impact, the adhering semi-conductive layer extruded between conductor and insulation, along with concentric copper conductor, secures restriction of electric field and resistance to partial discharges.

HRN HD 620 S1
IEC 60502-2
DIN VDE 0276 part 620


Datasheet NA2XS2Y 117.09 Kb

Construction

Construction

Technical data

Technical data

Conductor: Al round conductor, multi wire stranded compacted(RM), class 2 acc. to HRN HD 383 / IEC 60228 / DIN VDE 0295
Inner screen: extruded semi-conductive skin on conductor
Insulation: XLPE (cross-linked polyethylene, recent mark: PE-X) compound DIX 8 acc. to HRN HD 620 S1
External screen: extruded semi-conductive skin on insulation, longitudinally spliced with insulation (+tape of semi-conductive material)
Concentric conductor: in inner layer corrugated spirally wrapped copper wires, in external layer copper tape wrapped in counter-helix
Separating tape
Sheath: rigid PE (polyethylene) compound DMP 2 acc. to HRN HD 620 S1
sheath colour: black
Temperature range:  
during installation:
-20 °C up to +70 °C
max. operating temp.: +90 °C
at short circuit of max. 5 s: up to 250 °C
NYMboja.jpg
Minimal inner bending radius: 15D
Behaviour in fire: Halogen-free polyethylene sheath, but it is NOT self-extinguishing and fire-resistant acc. to IEC 60332-1


Dimensions – number of cores x conductor cross-section Construction External diameter External diameter Conductor diameter Insulation thickness Conductor resistance at20 °C Short circuit current 1s Cu weight Cable weight Packing*
    min. max. max. nom. max. nominal   approx.  
N x mm²   mm mm mm mm Ω/km A kg/km kg/km  
6/10 kV
1 x 50/16 RM 24 29 8,6 3,4 0,641 4,7 182 650 CUT
1 x 70/16 RM 26 31 10,2 3,4 0,443 6,58 182 736 CUT
1 x 95/16 RM 27 32 12,0 3,4 0,32 8,93 182 852 CUT
1 x 120/16 RM 29 34 13,5 3,4 0,253 11,3 182 950 CUT
1 x 150/16 RM 30 35 15,0 3,4 0,206 14,1 182 1100 CUT
1 x 150/25 RM 30 35 15,0 3,4 0,206 14,1 283 1128 CUT
1 x 185/16 RM 32 37 16,8 3,4 0,164 17,4 182 1250 CUT
1 x 185/25 RM 32 37 16,8 3,4 0,164 17,4 283 1269 CUT
1 x 240/16 RM 34 39 19,2 3,4 0,125 22,6 182 1400 CUT
1 x 240/25 RM 34 39 19,2 3,4 0,125 22,6 283 1473 CUT
1 x 300/25 RM 36 41 21,6 3,4 0,1 28,2 283 1679 CUT
1 x 400/35 RM 40 45 24,6 3,4 0,0778 37,6 394 2076 CUT
1 x 500/35 RM 43 48 27,6 3,4 0,0605 47 394 2439 CUT
12/20 kV
1 x 50/16 RM 28 33 8,6 5,5 0,641 4,7 182 806 CUT
1 x 70/16 RM 30 35 10,2 5,5 0,443 6,58 182 903 CUT
1 x 95/16 RM 31 36 12,0 5,5 0,32 8,93 182 1029 CUT
1 x 120/16 RM 33 38 13,5 5,5 0,253 11,3 182 1135 CUT
1 x 150/16 RM 34 39 15,0 5,5 0,206 14,1 182 1251 CUT
1 x 150/25 RM 34 39 15,0 5,5 0,206 14,1 283 1320 CUT
1 x 185/16 RM 36 41 16,8 5,5 0,164 17,4 182 1450 CUT
1 x 185/25 RM 36 41 16,8 5,5 0,164 17,4 283 1474 CUT
1 x 240/16 RM 39 44 19,2 5,5 0,125 22,6 182 1693 CUT
1 x 240/25 RM 39 44 19,2 5,5 0,125 22,6 283 1750 CUT
1 x 300/25 RM 41 46 21,6 5,5 0,1 28,2 283 1911 CUT
1 x 400/35 RM 44 49 24,6 5,5 0,0778 37,6 394 2330 CUT
1 x 500/35 RM 47 52 27,6 5,5 0,0605 47 394 2708 CUT
1 x 630/35 RM 50 55 29,3 5,5 0,0469 59,2 394 3177 CUT
18/30 kV
1 x 50/16 RM 33 38 8,6 8,0 0,641 4,7 182 1036 CUT
1 x 70/16 RM 35 40 10,2 8,0 0,443 6,58 182 1146 CUT
1 x 95/16 RM 36 41 12,0 8,0 0,32 8,93 182 1286 CUT
1 x 120/16 RM 38 43 13,5 8,0 0,253 11,3 182 1404 CUT
1 x 150/25 RM 39 44 15,0 8,0 0,206 14,1 283 1598 CUT
1 x 185/25 RM 41 46 16,8 8,0 0,164 17,4 283 1776 CUT
1 x 240/25 RM 43 48 19,2 8,0 0,125 22,6 283 2004 CUT
1 x 300/25 RM 46 51 21,6 8,0 0,1 28,6 283 2300 CUT
1 x 400/35 RM 49 54 24,6 8,0 0,0778 37,6 394 2682 CUT
1 x 500/35 RM 52 57 27,6 8,0 0,0605 47 394 3150 CUT

*) Packing: CUT = cable in different lengths on drum or reel, possible cutting at required length


Products