NA2XSY

Medium voltage single core cable 6/10 kV, 12/20 kV, 18/30 kV, XLPE insulated, PVC sheathed, with Al conductors and screen of Cu conductors

JUS mark: XHP48-A

NA2XSY
Application

Application

Standards

 

Medium voltage power cable for static application in ground, within and outside facilities, outdoor, in cable canals, in water, in conditions where cables are not exposed to heavier mechanical stress and tensile strain. Due to its very low factor of dielectric loss, which remains constant over its entire operating lifetime, and owing to excellent insulation property of XLPE-material, firmly longitudinally spliced with inner and external screen of semi-conductive material (extruded in one process), the cable has a high operating reliability. Used in transformer stations, switching blocks, in electric power plants and industrial plants. To avoid the effects of external impact, the adhering semi-conductive layer extruded between conductor and insulation, along with concentric copper conductor, secures restriction of electric field and resistance to partial discharges.

HRN HD 620 S1
IEC 60502-2
DIN VDE 0276 part 620


Datasheet NA2XSY 117.09 Kb

Construction

Construction

Technical data

Technical data

Conductor: Al round conductor, multi wire stranded compacted(RM), class 2 acc. to HRN HD 383 / IEC 60228 / DIN VDE 0295
Inner screen: extruded semi-conductive skin on conductor
Insulation: XLPE (cross-linked polyethylene, recent mark: PE-X) compound DIX 8 acc. to HRN HD 620 S1
External screen: extruded semi-conductive skin on insulation, longitudinally spliced with insulation (+tape of semi-conductive material)
Concentric conductor: in inner layer corrugated spirally wrapped copper wires, in external layer copper tape wrapped in counter-helix
Separating tape
Sheath: PVC compound DMV-6 acc. to HRN HD 620 S1
sheath colour: red
Temperature range:  
during installation:
-20 °C up to +70 °C
max. operating temp.: +90 °C
at short circuit of max. 5 s: up to 250 °C
NYMboja.jpg
Minimal inner bending radius: 15D


Dimensions – number of cores x conductor cross-section Construction External diameter External diameter Conductor diameter Insulation thickness Conductor resistance at20 °C Short circuit current 1s Cu weight Cable weight Packing*
    min. max. max. nom. max. nom.   approx.  
N x mm²   mm mm mm mm Ω/km A kg/km kg/km  
6/10 kV
1 x 50/16 RM 24 29 8,6 3,4 0,641 4,7 182 766 CUT
1 x 70/16 RM 26 31 10,2 3,4 0,443 6,58 182 861 CUT
1 x 95/16 RM 27 32 12,0 3,4 0,32 8,93 182 985 CUT
1 x 120/16 RM 29 34 13,5 3,4 0,253 11,3 182 1089 CUT
1 x 150/16 RM 30 35 15,0 3,4 0,206 14,1 182 1250 CUT
1 x 150/25 RM 30 35 15,0 3,4 0,206 14,1 283 1273 CUT
1 x 185/16 RM 32 37 16,8 3,4 0,164 17,4 182 1400 CUT
1 x 185/25 RM 32 37 16,8 3,4 0,164 17,4 283 1424 CUT
1 x 240/16 RM 34 39 19,2 3,4 0,125 22,6 182 1600 CUT
1 x 240/25 RM 34 39 19,2 3,4 0,125 22,6 283 1640 CUT
1 x 300/25 RM 36 41 21,6 3,4 0,1 28,2 283 1856 CUT
1 x 400/35 RM 40 45 24,6 3,4 0,0778 37,6 394 2350 CUT
1 x 500/35 RM 43 48 27,6 3,4 0,0605 47 394 2700 CUT
12/20 kV
1 x 50/16 RM 28 33 8,6 5,5 0,641 4,7 182 942 CUT
1 x 70/16 RM 30 35 10,2 5,5 0,443 6,58 182 1047 CUT
1 x 95/16 RM 31 36 12,0 5,5 0,32 8,93 182 1182 CUT
1 x 120/16 RM 33 38 13,5 5,5 0,253 11,3 182 1296 CUT
1 x 150/16 RM 34 39 15,0 5,5 0,206 14,1 182 1450 CUT
1 x 150/25 RM 34 39 15,0 5,5 0,206 14,1 283 1486 CUT
1 x 185/16 RM 36 41 16,8 5,5 0,164 17,4 182 1650 CUT
1 x 185/25 RM 36 41 16,8 5,5 0,164 17,4 283 1694 CUT
1 x 240/16 RM 39 44 19,2 5,5 0,125 22,6 182 1850 CUT
1 x 240/25 RM 39 44 19,2 5,5 0,125 22,6 283 1880 CUT
1 x 300/25 RM 41 46 21,6 5,5 0,1 28,2 283 2200 CUT
1 x 400/35 RM 44 49 24,6 5,5 0,0778 37,6 394 2600 CUT
1 x 500/35 RM 47 52 27,6 5,5 0,0605 47 394 3000 CUT
18/30 kV
1 x 50/16 RM 33 38 8,6 8,0 0,641 4,7 182 1184 CUT
1 x 70/16 RM 35 40 10,2 8,0 0,443 6,58 182 1302 CUT
1 x 95/16 RM 36 41 12,0 8,0 0,32 8,93 182 1450 CUT
1 x 120/16 RM 38 43 13,5 8,0 0,253 11,3 182 1575 CUT
1 x 150/25 RM 39 44 15,0 8,0 0,206 14,1 283 1774 CUT
1 x 185/25 RM 41 46 16,8 8,0 0,164 17,4 283 1951  
1 x 240/25 RM 43 48 19,2 8,0 0,125 22,6 283 2199 CUT
1 x 300/25 RM 46 51 21,6 8,0 0,1 28,6 283 2443 CUT
1 x 400/35 RM 49 54 24,6 8,0 0,0778 37,6 394 3000 CUT
1 x 500/35 RM 52 57 27,6 8,0 0,0605 47 394 3450 CUT

*) Packing: CUT = cable in different lengths on drum or reel, possible cutting at required length


Products




Proizvodi